Cause
The Fan is locked
Solution
Check the Connectors make sure they are secure. Check the wiring harness for defects.
Location of the Fan
While the fan can not be accessed easily, it can still be checked to either condemn it or validate it is good.
With the top of the unit off, and this metal cover removed, you can easily check the status of the Fan from this connector.
Connector for the Compressor and the Fan are located inside this protective bag.
Check the Resistance of the Fan Motor.
Test across any combination of the Yellow, Blue or Orange wires, the Fan is a BLDC fan and should Ohm equally across all terminals.
YL to BL = 9Ω – 12Ω
OR to BL = 9Ω – 12Ω
YL to OR = 9Ω – 12Ω
Voltage (read as A/C) should be approximately 70V to 90V.
Note: If any part of the sealed system or sensors or blower located on the Duct Assembly is defective, you must replace the whole Duct Assembly.